Full Text
SITE INFORMATION Address Location Date Time Performed By Adam Olheiser/Jordan Groves PRESSURE HYDRANT Location In front of 580 Ray J Glatt Static Pressure 55 psi Residual Pressure 50 psi 0 FLOW HYDRANT Location In front of Lincoln Elementary Pitot Pressure 42 psi Number of Outlets 1 outlets Outlet Diameter 2.5 inch Outlet Coefficient 0.9 Total Flow 1088 gpm EMERGENCY RESPONSE Pressure at Fire Flow 20 psi Expected Flow at 20 psi 3,111 gpm SYSTEM INFORMATION System Demand psi System Flow gpm Hose Included gpm SAFETY MARGIN Available Pressure at Demand Point - psi Safety Provided - psi WATER SUPPLY ANALYSIS 1025 N Boones Ferry Rd Along N Boones Ferry 7/24/2024 9:30 a.m. - 0, 55 1088, 50 600 900 1,200 1,500 1,800 2,100 2,400 2,700 3,000 3111, 20 0, 0 0, 0 0 10 20 30 40 50 60 70 80 Pressure (psi) Flow (gpm) WATER SUPPLY ANALYSIS ---PAGE BREAK--- SITE INFORMATION Address Location Date Time Performed By Adam Olheiser/Jordan Groves PRESSURE HYDRANT Location In front of 580 Ray J Glatt Static Pressure 55 psi Residual Pressure 54 psi 0 FLOW HYDRANT Location Beside 693 Ray J Glatt, corner of parking lot entrance Pitot Pressure 48 psi Number of Outlets 1 outlets Outlet Diameter 2.5 inch Outlet Coefficient 0.9 Total Flow 1163 gpm EMERGENCY RESPONSE Pressure at Fire Flow 20 psi Expected Flow at 20 psi 7,931 gpm SYSTEM INFORMATION System Demand psi System Flow gpm Hose Included gpm SAFETY MARGIN Available Pressure at Demand Point - psi Safety Provided - psi WATER SUPPLY ANALYSIS 693 Ray J. Glatt Circle Ray J Glatt Circle, North of Date 9:30 a.m. - 0, 55 1163, 54 1,600 2,400 3,200 4,000 4,800 5,600 6,400 7,200 8,000 7931, 20 0, 0 0, 0 0 10 20 30 40 50 60 70 80 Pressure (psi) Flow (gpm) WATER SUPPLY ANALYSIS