REQUEST FOR PROPOSALS BID 2020-02 Station 2 ADDENDUM NO. 2 ACKNOWLEDGEMENT OF RECEIPT Receipt of Addendum No. 2 to Bid 2020-02 to incorporate the following: • Updated Schedule of Items • Question and Answers • Asbestos Test Results • Engineering Plans / Drawings • Updated Geotechnical Report Receipt of addendum MUST be acknowledged and returned with bid package. DATE: FIRM NAME: ADDRESS: BY: ---PAGE BREAK--- 1. Will Fire Sprinklers be required Pending further information, fire sprinklers will be an option to add on once we hear back from B&S. 2. Will you be providing an updated Floor Plan that shows the Bathroom and 1,000 sf office/cleaning area See attach item floor plan 3. Will you be providing an updated Bid Form with the new line items Yes. 4. The Building Permit will be paid for by the Owner so the General Contractor will only be responsible for the MP&E Permits correct? County will pay for building permits. MP&E Permits are contractor responsibility. 5. Can you please provide the Soils Report See attach item updated GEORPT 6. Can you please provide the Asbestos Report. It was mentioned that this was done a long time ago so an update will need to be done. Updated report shows all samples as non-detect (Attached). 7. Can you please provide information on the swamp coolers that need to be installed. It was stated yesterday that the intent was to match another Pahrump Fire Station Master cool 7,000 CF 8. Will Propane piping need to be installed? No propane 9. Will the Space Heaters be Electric? Yes 10. Is the Concrete Paving around the Modular Building part of this scope of work? Add as an option 11. Due to us waiting on an updated Floor Plan can you extend the bid date so we have time to get it to the Subcontractors? Deadline changed to October 29th. 12. Will a Vehicle Exhaust System be required in the Bays? No 13. Sheet D1, note 5 states to "remove existing Metal Building, Concrete Slab & Foundation". There is also an Optional Item on the bid form to remove the existing Building. My understanding is that this scope of work will be covered under a separate Nye County Bid. Please clarify if this is actually part of the scope of work (as an optional price) for this project or if this will be done prior to this project construction start date This is just an option at this time. 14. Exhibit A: Scope of Work, under grading it states that the Grading Work will be completed prior to award. Please confirm that this will be done prior to the project construction start date. Also, will the pad be over- ex'd or does that need to be included in our scope of work for this specific project? If the Building is not being removed under a different contract prior to this projects start date, will the Grading still be done under another contract and not be part of this projects scope of work? Grading will be completed before the construction start date. 15. There is no mention of Building or Site Electrical. Please confirm that no Electrical work is required under the scope of work for this specific project. See attach item Electrical and Lighting add as an option with 400 amp service 16. There is no mention of Plumbing. Please confirm that no Plumbing work is required under the scope of work for this specific project See attach item plumbing add as an option ---PAGE BREAK--- 17. Sheet G1 shows a Modular building being put on the site. Please confirm that this is not park of the scope of work for this specific project. Not park of the scope of work 18. Sheet G1, note 2 calls for a 6" slab with #3 bars at 18" o.c. Sheet S2 calls for an 8" slab with #4 bars at 15 o.c. Please confirm this slab needs to be 8" per the Structural drawings. 8” per Structural drawings 19. Does the Owner Supplied Pre-Engineered Building come with the Roll up Doors? Roll up doors as add option ---PAGE BREAK--- ---PAGE BREAK--- Approved by: Approved Signatory Renee Report for: Tomokazu Taniuchi NOVA Geotechnical & Inspection Services 4480 W. Hacienda Ave. Suite 104 Las Vegas, NV 89118 Regarding: Project: E-20-107; Nye County Fire Station 2 Pre-Demo Asbestos Inspection EML ID: 2504300 All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with asbestos concentration can be provided when requested. Eurofins EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor. Dates of Analysis: Asbestos PLM: 10-19-2020 Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 500031-0 EMLab ID: 2504300, Page 1 of 4 Aerotech Laboratories, Inc. ---PAGE BREAK--- Eurofins EMLab P&K 1501 West Knudsen Drive, Phoenix, AZ 85027 (800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: NOVA Geotechnical & Inspection Services C/O: Tomokazu Taniuchi Re: E-20-107; Nye County Fire Station 2 Pre-Demo Asbestos Inspection Date of Sampling: 10-16-2020 Date of Receipt: 10-19-2020 Date of Report: 10-19-2020 ASBESTOS PLM REPORT Total Samples Submitted: 9 Total Samples Analyzed: 9 Total Samples with Layer Asbestos Content > 0 Location: PLM-1, Orange Peel Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931176-1 Sample Layers Asbestos Content White Paint ND White Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor Location: PLM-2, Orange Peel Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931177-1 Sample Layers Asbestos Content White Paint ND White Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor Location: PLM-3, Orange Peel Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931178-1 Sample Layers Asbestos Content White Paint ND White Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor EMLab ID: 2504300, Page 2 of 4 Aerotech Laboratories, Inc. The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. ‡ A "Version" indicated by after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of ---PAGE BREAK--- Eurofins EMLab P&K 1501 West Knudsen Drive, Phoenix, AZ 85027 (800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: NOVA Geotechnical & Inspection Services C/O: Tomokazu Taniuchi Re: E-20-107; Nye County Fire Station 2 Pre-Demo Asbestos Inspection Date of Sampling: 10-16-2020 Date of Receipt: 10-19-2020 Date of Report: 10-19-2020 ASBESTOS PLM REPORT Location: PLM-4, 12" x 12" Tan Floor Tile and Mastic Lab ID-Version‡: 11931179-1 Sample Layers Asbestos Content Tan Floor Tile ND Yellow Mastic ND Sample Composite Homogeneity: Moderate Location: PLM-5, 12" x 12" Tan Floor Tile and Mastic Lab ID-Version‡: 11931180-1 Sample Layers Asbestos Content Tan Floor Tile ND Yellow Mastic ND Sample Composite Homogeneity: Moderate Location: PLM-6, 12" x 12" Tan Floor Tile and Mastic Lab ID-Version‡: 11931181-1 Sample Layers Asbestos Content Tan Floor Tile ND Yellow Mastic ND Sample Composite Homogeneity: Moderate EMLab ID: 2504300, Page 3 of 4 Aerotech Laboratories, Inc. The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. ‡ A "Version" indicated by after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of ---PAGE BREAK--- Eurofins EMLab P&K 1501 West Knudsen Drive, Phoenix, AZ 85027 (800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: NOVA Geotechnical & Inspection Services C/O: Tomokazu Taniuchi Re: E-20-107; Nye County Fire Station 2 Pre-Demo Asbestos Inspection Date of Sampling: 10-16-2020 Date of Receipt: 10-19-2020 Date of Report: 10-19-2020 ASBESTOS PLM REPORT Location: PLM-7, Popcorn Ceiling Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931182-1 Sample Layers Asbestos Content White Paint ND White Ceiling Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor Location: PLM-8, Popcorn Ceiling Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931183-1 Sample Layers Asbestos Content White Paint ND White Ceiling Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor Location: PLM-9, Popcorn Ceiling Drywall System (Paint, Texture, Tape, Joint Compound, Drywall) Lab ID-Version‡: 11931184-1 Sample Layers Asbestos Content White Paint ND White Ceiling Texture ND Cream Tape ND White Joint Compound ND White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor EMLab ID: 2504300, Page 4 of 4 Aerotech Laboratories, Inc. The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. ‡ A "Version" indicated by after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of ---PAGE BREAK--- LAS VEGAS, NV 89146 T: [PHONE REDACTED] F: [PHONE REDACTED] gcwengineering.com 1555 S. RAINBOW BLVD. ENGINEERS SURVEYORS LAS VEGAS, NV 89146 T: [PHONE REDACTED] F: [PHONE REDACTED] gcwengineering.com 1555 S. RAINBOW BLVD. ENGINEERS SURVEYORS 398-A914 TOWN OF PAHRUMP PAHRUMP VALLEY FIRE AND RESCUE STATION #2 S2 FOUNDATION PLAN ---PAGE BREAK--- WH R R GFI GFI GFI GFI 3 3 3 - - - - Date Drawn by Checked by Electrical Electrical Issue Date Author Checker 1/8" = 1'-0" 1 Level 1 Electrical ---PAGE BREAK--- WH - - - - 3' - 0" 13' - 0" 4' - 6" 13' - 0" 4' - 0" 13' - 0" 5' - 0" 13' - 0" 5' - 0" 13' - 0" 4' - 0" 13' - 0" 6' - 6" 110' - 0" 60' - 0" 118 SF Laundry 95 SF Room 38 SF Janitor 152 SF BioRoom 50 SF BathRoom 20' - 0" 30' - 0" 16' - 0" 1' - 0" 12' - 6" 10' - 0" 0' - 6" 9' - 0" 10' - 0" 1' - 0" 8' - 0" 10' - 6" 1/8" = 1'-0" 1 Level 1 Date Drawn by Checked by floorplan floorplan Issue Date Author Checker ---PAGE BREAK--- - - - - - Date Drawn by Checked by lighting Lighting Issue Date Author Checker 1/8" = 1'-0" 1 Level 1 lighting ---PAGE BREAK--- WH - - - - Date Drawn by Checked by Plumbing Plumbing Issue Date Author Checker 1/8" = 1'-0" 1 Level 1 Plumbing