Full Text
Scale: No Scale Detail - Residential Street Light A Precast Concrete Base Collar Road base fill 90% Compaction in 6 Inch Lifts or Flowable Fill. Notes: 1) All Construction to meet National Electric Code. 2) No Excavation Within 8' of Pole Foundation. 3) Undisturbed Native Gravel or 90% Compacted Road Base in 6" Lifts. 4) Mark Junction Box Lids "Street Lights". 5) Wires From Utility Co. Transformer or Secondary Box to Junction Box to be Single Conductor URD Rated #6 Stranded Copper Cable Type Use-2 or RHH or RHW-2 60 Mils XLP. 6) Fuse Hot Wire in Junction Box. Supply Splice Kit for Neutral. 7) Contractor to Install Junction Box With Fuse. Box to be Located with in 4 Feet from Utility Co. Transformer or Secondary Box. Leave Pigtail 8 Feet Long to Transformer or Secondary Box. Utility Co. to Make Connection. 8) Contractor Shall Provide All Necessary Parts and Labor for Installation of Street Lights. 9) Each Street Light shall Have A Junction Box With Fuse. 10) Street Lights Should be a Minimum of 5 feet from Drive Way. 11) All Trenches to be Inspected by City Inspector. 12) Notify City 2 Weeks Before Installation of Street Lights. Ground Surface Residential Street Light Underground Detail Direct Burial Cable Pigtail 8' Long to From Secondary to Transformer See Note 2 for Paved Trench Repair Sand Direct Burial Cable Water Line Scale: No Scale Detail - Residential Branch Circuit Trench A Magnetic Marker Tape Backfill Rocky Moutian Power Source/Transformer Scale: No Scale Detail - Junction Box With Fuse B Ground Wires Neutral Wires Hot Leg With Fuse Carson L 1419-12 Box Detail - Residential Branch Circuit Trench RD-08 A Detail - Junction Box With Fuse B 10' Max. Min.