Full Text
FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS SYS PLN MGR SUB MAINT NEW SHEET NEW SHEET N/A N/A SR ELEC ENG. CITY OF ANAHEIM STREET LIGHT DESIGN #746 ANAHEIM RESORT AREA L133 REV4 4 6/17/19 1 2 L 133 SCOPE: THIS STANDARD SHOWS CONSTRUCTION AND DETAILS OF CITY OF ANAHEIM STREET LIGHT SPECIAL DESIGN #746 FOR ANAHEIM RESORT AREA. POLE LENGTH 23'-1" CURB FACE 30" OR 48" BASE DETAIL CL MAST ARM L RAIL (BY OTHERS) CONCRETE BRIDGE 3" & HANDHOLE CL 8'-0" 26'-4" 7GA. 12 FLUTE GALV. STEEL POLE (.14"/FT. TAPER) FINIAL LUMINAIRE (SEE TABLE) FLUTED POLE 4" X 6" HANDHOLE IN POLE BOLT PROJECTION 7 1/2" DIA. 11" DIA. x 3/4" THICK BASE 1 1/4" HOLES ON 9 1/4" BOLT CIRCLE SQUARE BASE CAP TOP OF BRIDGE RAIL BRIDGE RAIL TOP OF 1"PVC SCH 80 CONDUIT(S) (OR AS SHOWN ON W.O. DWG.) STUB-UP INTO BASE OF STREET LIGHT. CONDUIT(S) TO EXIT ON C OF FOUNDATION, PARALLEL TO CURB, OR AS SHOWN ON W.O. DWG. CAP ALL UNUSED CONDUITS 4-1" X 36" X 4" GALV. ANCHOR RODS WITH 2 WASHERS & 2 NUTS PER ROD BASE PLATE DETAIL ---PAGE BREAK--- FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS SYS PLN MGR SUB MAINT NEW SHEET NEW SHEET N/A N/A SR ELEC ENG. CITY OF ANAHEIM STREET LIGHT DESIGN #746 ANAHEIM RESORT AREA L133 REV4 4 6/17/19 2 2 L 133 ITEM QTY DESCRIPTION ANAHEIM PART NO. (ARA) ANAHEIM PART NO. (GSB) COMPATIBLE UNITS (ARA) COMPATIBLE UNITS (GSB) - - POLE WITH MAST ARM. SCROLL WORK, SQUARE BASE CAP AND ANCHOR BOLTS- ANAHEIM TYPE SA3-BRIDGE MOUNT - - SLDES746-P7 - 1 1 23'-1" POLE, STEEL, FLUTE 476280 - - - 2 2 SQUARE BASE CAP (SA2-SA3) 476305 - - - 3 1 8' ARM W/ SCROLL & FINIAL 464050 - - - 4 1 LUMINAIRE (PAINT COLOR, NOTE 9) 400W-120/208/240/277 474277 - L400LED-P7* - 250W-120/208/240/277 474247 - L250LED-P7* - 200W-120/208/240/277 474241 - L200LED-P7* - NOTES: 1. STEEL TO BE HIGH TENSILE STRENGTH. CAST ALUMINUM TO BE 319 ALLOY OR AS SPECIFIED. 2. ALL FASTERNERS TO BE STAINLESS STEEL. 3. WIRING SHALL BE #14 COPPER XHHW-2 MINIMUM WIRES-(BLACK-PHASE, WHITE-NEUTRAL, GREEN-GROUND). 4. COMPATIBLE UNIT FOR ITEM 1 OF BILL OF MATERIAL TABLE, INCLUDES, POLE, MAST ARM AND THE CAST BASES. COMPATIBLE UNIT FOR ITEM 4 OF MATERIAL TABLE INCLUDES LAMP AND PHOTO CONTROL. 5. POLE SHAFT AND ALL STEEL COMPONENTS SHALL BE HOT-DIP GALVANIZED (HDG) TO ASTM A123 PRIOR TO FINISHING PROCEDURE. 6. FINISH FOR ANAHEIM RESORT AREA (ARA): a. ALL ITEMS EXCEPT FINIAL SHALL BE GREEN, SEMI-GLOSS ANAHEIM P7-GREEN, "PPG-AMERSHIELD" "PANTONE 330C" b. FINIAL SHALL BE FROM MATTHEWS PAINT CO, AZTEC GOLD- INTESTATE 286-401 G. 7. FINISH FOR GRADE SEPARATION AND BRIDGES (GSB): a. ALL ITEMS EXCEPT FINIAL SHALL BE BLACK-GRAY,SEMI-GLASS" PPG-AMERSHIELD RAL 7021. b. FINIAL SHALL BE SILVER RAL # 9006. 8. THE PAINTING PROCEDURE OF HDG SURFACES SHOULD BE SUBMITTED TO ANAHEIM STANDARDS GROUP FOR REVIEW AND APPROVAL 9. LUMINAIRE SHALL BE PAINTED SAME AS POLE ORDERED, OR PAINTED BY THE CONTRACTOR TO MATCH POLE COLOR. 10. THE POLE AND MAST ARM MANUFACTURER IS SOUTHCOAST LIGHTING AND COBRA HEAD LUMINAIRE MANUFACTURER IS "GENERAL ELECTRIC". VENDORS TO ORDER THE UNIT ARE SOUTH COAST LIGHTING, ONE-SOURCE, WESCO AND INDEPENDENT ELECTRIC. 11. THE HAND HOLES ON POLE SHOULD LINE UP WITH HAND HOLE ON BASE FOR EASY ACCESS TO CABLES. 12. DRILL AND TAP THE POLE FOR SIGNAGE. 13. TO ATTACH THE MAST ARM TO POLE, TORQUE THE SETSCREWS @ 21 FT-LBS. 14. FOOTING (FOUNDATION) CONCRETE MIX SHALL BE 560-C-3250. 15. DESIGNER SHALL USE APPROPRIATE PHOTOMETRIC SOFTWARE TO CONFIRM IES GUIDELINES ARE FOLLOWED PRIOR TO STREETLIGHT INSTALLATION. * FOR LED EQUAL CONTACT T & D STANDARD GROUP.