APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT FILENAME: REVISION KEYS: ADDED / REVISED TEXT NEW SHEET CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : FIELD MGR OPER. MGR T&D CONSTRUCTION STANDARDS 4' x 4' VAULT WITH COVER FOR 12KV JUNCTIONS CU1600-14A REV5 5 01-11 1 2 CU 1600-14A BOTTOM SECTION 12"X16"X12" KNOCKOUTS EACH CORNER 8"DIA x 4"DEEP SUMP KNOCKOUT GALV. PULL IRON (2 PLACES) SECTION TOP SECTION EXTENSION 35" 12" 6" 53" OVERALL HEIGHT 1" DIA. GROUND ROD HOLE 16" DASHED LINE REPRESENTS BASE SEPERATION FOR INTERCEPT STYLE 56" 56" 30" 5" 27" 1k" x 1k" x 36" LONG, 12GA., HOT DIP GALV., UNISTRUT CONCRETE INSERT. SET FLUSH WITH INSIDE WALL (TYP. 4 WALLS). C L 6" TYP. 4" - 6" 12" 4'-0" 4'-0" 4" CENTERLINE OF INSERT TO BE 27" ABOVE FLOOR 4448IHL 4448IHL 4448HL 4448HL UTILITY VAULT PKWY TRFC INTERCEPT TRFC PKWY USE STANDARD STYLE K44-FP48-16P JENSEN K44-FP48-16T K44-FI48-16P K44-FI48-16T * UTILITY VAULT DESIGN HAS A SEPARATE EXTENSION SECTION, THE OUTSIDE DIMENSION IS 58 INCHES AND THE USAGE SHALL BE IDENTIFIED AT THE TIME OF ORDER. * (UTILITY VAULT) RPM PARKWAY OR GALVANIZED TRAFFIC COVER MARKED "ELECTRIC", WITH HOLD DOWN FASTENERS AND 1" DIA. LIFTING HOLES WITH GALV. TAMPERPROOF PLATE BELOW SCOPE: THIS STANDARD SHOWS REQUIREMENT FOR EASEMENT AND INSTALLATION FOR A 4' x 4' VAULT WITH COVER FOR 12KV JUNCTIONS. ELECTRIC (2 PLACES) MAINTENANCE ONLY ---PAGE BREAK--- APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT FILENAME: REVISION KEYS: ADDED / REVISED TEXT NEW SHEET CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : FIELD MGR OPER. MGR T&D CONSTRUCTION STANDARDS 4' x 4' VAULT WITH COVER FOR 12KV JUNCTIONS CU1600-14A REV5 5 01-11 2 2 CU 1600-14A 6" (POWER) 4"C (CONTROL) 2"C 6" SPACING INSTALL VERTICAL WITH PREFERRED NOTES: PER WORK ORDER DRAWINGS (SEE NOTE E & F) CU 1600-20 AND SIZED PAD AND VAULT PER PADMOUNT TRANSFORMER (SEE NOTE E) COVER, ALTERNATE LOCATION 4' X 4' VAULT WITH SEE CU 1600-4A (SEE NOTE E) ALTERNATE LOCATION 4' X 4' VAULT WITH COVER, WITH COVER, LOCATION PRIMARY CONDUIT RUNS AS SPECIFIED IN WORK ORDER DRAWINGS 4' X 4' VAULT 1-2" & 1-4" PVC CONDUIT SCHED. 40 MIN. 12" MIN. SEE NOTE F LOCATION DETAIL WITH PADMOUNT TRANSFORMER A. VAULT CONSTRUCTION SHALL MEET APPLICABLE REQUIREMENTS OF THE LATEST REVISED EDITION OF THE FOLLOWING STANDARDS: AC 1318, ASTM C-857 & AASHTO (WHICH INCLUDES AASHTO H-20 TRAFFIC WHEEL LOADING). B. EXCAVATION PER CU 1600-4B, MINIMUM SIZE: 72" X 72" X DEPTH REQUIRED. C. ALL JOINTS SHALL BE GASKETED AND WATERTIGHT. D. ONLY TONGUE AND GROVE GRADE RINGS SHALL BE ADDED FOR GREATER DEPTHS. E. WHEN INSTALLED IN CONJUNCTION WITH PADMOUNT TRANSFORMER PAD AND VAULT INSTALLATION, SEE LOCATION DETAIL ABOVE OR AS SPECIFIED ON WORK ORDER DRAWINGS. F. FOR ALTERNATE LOCATIONS SHOWN ABOVE, THIS DIMENSION SHALL BE: 18" MIN. WITH 6' X 8' TRANSFORMER PAD 30" MIN. WITH 8' X 10' TRANSFORMER PAD G. INSTALL EQUIPMENT PROTECTIVE POSTS PER CU 1600-9 AND AS SHOWN ON WORK ORDER DRAWINGS OR REQUIRED BY UTILITY ELECTRICAL INSPECTOR. 8' EASEMENT 2' 4' 2' 8' EASEMENT 4' 2' 2' 4'x4' EASEMENT CLEARANCE REQUIREMENT MAINTENANCE ONLY