Full Text
FACE CURB SIDEWALK 8' MIN. (TYP.) 8' MIN. (TYP.) 4' SIDEWALK CURB FACE 4' 8' MIN. (TYP.) PER ENGINEERING DWG. CONDUIT ARRANGEMENT 1' MIN. 1' MIN A 4' A DETAIL 2A CLEARANCE AREA (SEE NOTE 3 & 4) OPTION 1 DETAIL 2B MIN. MIN. MIN. SCOPE: THIS STANDARD SHOWS INSTALLATION AND CONDUIT ARRANGEMENT FOR 12KV PADMOUNT PMC & PME SWITCHES. UPDATED TO MOVE OPTION 1 TO MAINTENANCE FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT T&D CONSTRUCTION STANDARDS SUB MAINT NEW SHEET NEW SHEET 12KV PADMOUNT SWITCH VAULT INSTALLATION AND CONDUIT ARRANGEMENT CU1600-5 REV10 10 01-16 1 3 CU 1600-5 ---PAGE BREAK--- FACE CURB SIDEWALK SIDEWALK CURB FACE PER ENGINEERING DWG. CONDUIT ARRANGEMENT 1' MIN. 1' MIN. OPTION 2 CLEARANCE AREA (SEE NOTE 3 & 4) 8' MIN. 8' MIN. 4' MIN. 8' MIN. 4' MIN. 4' MIN. 8' WORKING CLEARANCE (SEE NOTE 6) DETAIL 3A DETAIL 3B A A UPDATED TO MOVE OPTION 1 TO MAINTENANCE FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT T&D CONSTRUCTION STANDARDS SUB MAINT NEW SHEET NEW SHEET 12KV PADMOUNT SWITCH VAULT INSTALLATION AND CONDUIT ARRANGEMENT CU1600-5 REV10 10 01-16 2 3 CU 1600-5 ---PAGE BREAK--- TABLE 1 NOTES: 1. 2. FOR ACTUAL INSTALLATIONS AND CONDUIT SIZES, REFER TO WORKING DRAWINGS. 3. PUBLIC UTILITY EASEMENT IS REQUIRED FOR INSTALLATION OF EQUIPMENT OR FACILITIES OUTSIDE THE PUBLIC RIGHT-OF-WAY. NO OTHER UTILITY OR PRIVATE EQUIPMENT PULL BOXES, ABOVE GROUND PEDESTALS, OROBSTRUCTION OF ANY KIND SHALL BE INSTALLED WITHIN THE CLEARANCE/PUE AREA OR SIDEWALK FRONTING CLEARANCE AREA. 4. CLEARANCE AREA IS TO BE COVERED WITH 4" SIDEWALK QUALITY CONCRETE. 5. SEE CU 1600-4B FOR EXCAVATION DETAILS. FOR MINIMUM SIZE SEE MANUFACTURES SUGGESTIONS. 6. MAINTAIN 8' WORKING CLEARANCES SHOWN ON DETAIL 3B. OPTION CABLE VAULT SIZE REFERENCE CONST. STANDARD A EASEMENT REQUIRED 2A 11'-4" X 6'-3 1/2" CU-1600-3J 20'-4" 14'-31 2" X 20'-4" 2B 11'-4" X 6'-3 1/2" CU-1600-3J 27'-4" 11'-31 2" X 27'-4" 3A 11'-4" X 6'-3 1/2" CU-1600-3J 16'-4" 22'-31 2" X 16'-4" 3B 11'-4" X 6'-3 1/2" CU-1600-3J 19'-4" 15'-31 2" X 19'-4" (NOTE 6) UPDATED TO MOVE OPTION 1 TO MAINTENANCE FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT T&D CONSTRUCTION STANDARDS SUB MAINT NEW SHEET NEW SHEET 12KV PADMOUNT SWITCH VAULT INSTALLATION AND CONDUIT ARRANGEMENT CU1600-5 REV10 10 01-16 3 3 CU 1600-5