Full Text
NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 1 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.1 – PLANNING AND DESIGN (Site Development) 5.106.1 Storm Water Pollution Prevention Plan Newly constructed projects which disturb less than one acre of land shall prevent the pollution of storm water runoff from the construction activities through one or more of the following measures: 5.106.1.1 Local ordinance Comply with a lawfully enacted storm water management and/or erosion control ordinance. 5.106.1.2 Best management practices (BMP) Prevent the loss of soil through wind or water erosion by implementing an effective combination of erosion and sediment control and good housekeeping BMP. 1. Soil loss BMP that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a. Scheduling construction activity b. Preservation of natural features, vegetation and soil c. Drainage swales or lined ditches to control storm water flow d. Mulching or hydroseeding to stabilize disturbed soils e. Erosion control to protect slopes f. Protection of storm drain inlets (gravel bags or catch basin inserts) g. Perimeter sediment control (perimeter silt fence, fiber rolls) h. Sediment trap or sediment basin to retain sediment on site i. Stabilized construction exits j. Wind erosion control k. Other soil loss BMP acceptable to the enforcing agency 2. Good housekeeping BMP to manage construction equipment, materials, and wastes that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a. Material handling and waste management b. Building materials stockpile management c. Management of washout areas (concrete, paints, stucco, etc.) d. Control of vehicle/equipment fueling to contractor’s staging area e. Vehicle and equipment cleaning performed off site f. Spill prevention and control g. Other housekeeping BMP acceptable to the enforcing agency 5.106.4 Bicycle Parking Comply with Sections 5.106.4.1 and 5.106.4.2; or meet local ordinance, whichever is stricter. 5.106.4.1 Short-term bicycle parking If the project is anticipated to generate visitor traffic, provide permanently anchored bicycle racks within 200 feet of the visitors’ entrance, readily visible to passers-by, for 5 percent of visitor motorized vehicle parking capacity, with a minimum of one two-bike capacity rack. 5.106.4.2 Long-term bicycle parking For buildings with over 10 tenant-occupants, provide secure bicycle parking for 5 percent of motorized vehicle parking capacity, with a minimum of one space. Acceptable parking facilities shall be convenient from the street and may include: 1. Covered, lockable enclosures with permanently anchored racks for bicycles; 2. Lockable bicycle rooms with permanently anchored racks; and 3. Lockable, permanently anchored bicycle lockers. Note: Additional information on recommended bicycle accommodations may be obtained from Sacramento Area Bicycle Advocates. 5.106.5.2 Designated Parking Provide designated parking for any combination of low-emitting, fuel efficient, and carpool/van pool vehicles per Table 5.106.5.2. 5.106.5.2.1 Parking Stall Marking Paint, in the paint used for stall striping, the following characters such that the lower edge of the last word aligns with the end of the stall striping and is visible beneath a parked vehicle: CLEAN AIR/ VANPOOL/EV Note: Vehicles bearing Clean Air Vehicle stickers from expired HOV lane programs may be considered eligible for designated parking spaces. 5.106.8 Light Pollution Reduction Outdoor lighting systems shall be designed and installed to comply with the following: 1. The minimum requirements in the California Energy Code for Lighting Zones 1-4 as defined in Chapter 10 of the California Administrative Code; and 2. Backlight, Uplight and Glare (BUG) ratings as defined in IESNA TM-15-11; and 3. Allowable BUG ratings not exceeding those shown in Table 5.106.8, or Comply with a local ordinance lawfully enacted pursuant to Section 101.7, whichever is more stringent. Exceptions: 1. Luminaires that qualify as exceptions in Section 147 of the California Energy Code 2. Emergency lighting Note: See also California Building Code, Chapter 12, Section 1205.6 for college campus lighting requirements for parking facilities and walkways. TABLE 5.106.8 [Table not shown for clarity, refer to Code] 5.106.8.1 Effective date Newly constructed nonresidential projects with outdoor lighting for which an application for a building permit is submitted on or after July 1, 2012 shall comply with this section. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 2 of 17 5.303.1.2 Excess consumption Any building within a project or space within a building that is projected to consume more than 1,000 gal/day. 5.303.2 Twenty percent savings A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 20% shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fittings as required by the California Building Standards Code. The 20% reduction in potable water use shall be demonstrated by one of the following methods. 1. Prescriptive method. Each plumbing fixture and fitting shall not exceed the maximum flow rate at ≥20 percent reduction as specified in Table 5.303.2.3, or 2. Performance method. A calculation demonstrating a 20% reduction in the building “water use baseline” as established in Table 5.303.2.2 shall be provided. [Tables 5.303.2.2 and 5.303.2.3 are not shown for clarity, but these footnotes have been added to the tables: Footnotes for Table 5.303.2.2: 2 Refer to Table A, Chapter 4, California Plumbing Code, for occupant load factors. Shower use by occupants depends on the type of use of a building or portion of a building, e.g., total occupant load for a health club, but only a fraction of the occupants in an office building as determined by the anticipated number of users. Nonresidential kitchen faucet use is determined by the occupant load of the area served by the fixture. Footnotes for Table 5.303.2.3: 1 Lavatory Faucets Residential shall not have a flow rate less than 0.8 gpm at 20 psi. 2 Kitchen faucets may temporarily increase flow above the maximum rate, but not above 2.2 gpm @ 60 psi and must default to a maximum flow rate of 1.8 gpm @ 60 psi. 3 Where complying faucets are unavailable, aerators rated at .35 gpm or other means may be used to achieve reduction. 5.303.2.1 Multiple showerheads serving one shower When a shower is served by more than one showerhead, the combined flow rate of all the showerheads controlled by a single valve shall not exceed the maximum flow rate at ≥20 percent reduction contained in Table 5.303.2.2 or the shower shall be designed to only allow one showerhead to be in operation at a time. Exception: The maximum flow rate for shower heads when using the performance method specified in Section 5.303.2.1, Item 2 is 2.5 gpm @ 80 psi. 5.303.4 Wastewater reduction Each building shall reduce by 20% wastewater by one of the following methods: 1. [DSA-SS] The installation of water-conserving fixtures (water closets, urinals) meeting the criteria established in sections 5.303.2 or 5.303.3 or 2. Utilizing non-potable water systems [captured rainwater, graywater, and municipally treated wastewater (recycled water) complying with the current edition of the California Plumbing Code or other methods described in Section A5.304]. SECTION CREDIT REQUIREMENTS PC INSP Division 5.1 – PLANNING AND DESIGN (Site Development) (Continued) 5.106.10 Grading and Paving Construction plans shall indicate how site grading or a drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following: 1. Swales 2. Water collection and disposal systems 3. French drains 4. Water retention gardens Division 5.2 – ENERGY EFFICIENCY 5.201.1 Scope For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory building standards. Note: It is the intent of this code to encourage buildings to achieve exemplary performance in the area of energy efficiency. For the purposes of energy efficiency standards, the California Energy Commission believes specifically, a green building should achieve at least a 15% reduction in energy usage when compared to the State’s mandatory energy efficiency standards. Division 5.3 – WATER EFFICIENCY AND CONSERVATION (Indoor Water Use) 5.303.1 Meters Separate meters or metering device shall be installed for the uses described in Sections 503.1.1 and 503.1.2. 5.303.1.1 Buildings in excess of 50,000 square feet (4645 m2) Separate submeters shall be installed as follows: 1. For each individual leased, rented, or other tenant space within the building projected to consume more than 100 gal /day (380 L/day), including, but not limited to, spaces used for laundry or cleaners, restaurant or food service, medical or dental office, laboratory, or beauty salon or barber shop. 2. Where separate submeters for individual building tenants are unfeasible, for water supplied to the following a. Makeup water for cooling towers where flow through is greater than 500 gpm (30 L/s) b. Makeup water for evaporative coolers greater than 6 gpm (0.04 L/s) c. Steam and hot-water boilers with energy input more than 500,000 Btu/h (147 kW) ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 3 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.3 – WATER EFFICIENCY AND CONSERVATION (Indoor Water Use) (Continued) 5.303.6 Plumbing fixtures and fittings Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall meet the standards referenced in Table 5.503.6. . [Table 5.303.6 is not shown for clarity, but referenced standard ASME 112.18.1/CSA B125.1 was added in the table for showerheads with a maximum flow rate of 2.5 gal (9.5l.)/min.] 5.304.1 Water budget A water budget shall be developed for landscape irrigation use that conforms to the local water efficient landscape ordinance or to the California Department of Water Resources Model Water Efficient Landscape Ordinance where no local ordinance is applicable. Note: Prescriptive measures to assist in compliance with the water budget are listed in Sections 492.5 through 492.8, 492.10 and 492.11 of the ordinance, which may be found at: http://www.owue.water.ca.gov/landscape/ord/ord.cfm Division 5.3 – WATER EFFICIENCY AND CONSERVATION (Outdoor Water Use) 5.304.2 Outdoor potable use For new water service for landscaped areas of at least 1000 square feet but not more than 5000 square feet (the level at which Water Code §535 applies), separate submeters or metering devices shall be installed for outdoor potable water use.. 5.304.3 Irrigation design In new nonresidential construction with at least 1000 square feet but not more than 2500 square feet of landscaped area (the level at which the MLO applies), install irrigation controllers and sensors which include the following criteria, and meet manufacturer’s recommendations. 5.304.3.1 Irrigation controllers Automatic irrigation system controllers installed at the time of final inspection shall comply with the following: 1. Controllers shall be weather- or soil moisture-based controllers that automatically adjust irrigation in response to changes in plants' needs as weather conditions change. 2. Weather-based controllers without integral rain sensors or communication systems that account for local rainfall shall have a separate wired or wireless rain sensor which connects or communicates with the controller(s). Soil moisture-based controllers are not required to have rain sensor input. Note: More information regarding irrigation controller function and specifications is available from the Irrigation Association at: http://www.irrigation.org/SWAT/Industry/ia-tested.asp Division 5.4 - MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Water Resistance and Moisture Management) 5.407.1 Weather protection Provide a weather-resistant exterior wall and foundation envelope as required by California Building Code Section 1403.2 (Weather Protection) and California Energy Code Section 150, (Mandatory Features and Devices), manufacturer’s installation instructions, or local ordinance, whichever is more stringent. 5.407.2 Moisture control Employ moisture control measures by the following methods. 5.407.2.1 Sprinklers Design and maintain landscape irrigation systems to prevent spray on structures. 5.407.2.2 Entries and openings Design exterior entries and/or openings subject to foot traffic or wind-driven rain to prevent water intrusion into buildings. Notes: 1. Use features such as overhangs and recesses, and flashings integrated with a drainage plane. 2. Use non-absorbent floor and wall finishes within at least two feet around and perpendicular to such openings. Division 5.4 – MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Construction Waste Reduction, Disposal & Recycling) 5.408.1 Construction Waste Management Recycle and/or salvage for reuse a minimum of 50 percent of the non-hazardous construction waste in accordance with Section 5.408.1.1, 5.408.1.2 or 5.408.1.3; or meet a local construction and demolition waste management ordinance, whichever is more stringent. 5.408.1.1 Construction waste management plan Where a local jurisdiction does not have a construction and demolition waste management ordinance that is more stringent, submit a construction waste management plan for approval by the enforcement agency that: 1. Identifies the materials to be diverted from disposal by efficient usage, recycling, reuse on the project, or salvage for future use or sale. 2. Determines if materials will be sorted on-site (source-separated) or bulk mixed (single stream). 3. Identifies diversion facilities where material collected will be taken. 4. Specifies that the amount of materials diverted shall be calculated by weight or volume, but not by both. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 4 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.4 – MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Construction Waste Reduction, Disposal & Recycling) (Continued) 5.408.1.2 Waste Management Company Utilize a waste management company that can provide verifiable documentation that the percentage of construction waste material diverted from the landfill complies with this section. Note: The owner or contractor shall make the determination if the construction waste material will be diverted by a waste management company. Exceptions to 5.408.1.1 and 5.408.1.2: 1. Excavated soil and land-clearing debris 2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist. 3. Demolition waste meeting local ordinance or calculated in consideration of local recycling facilities and markets, where demolition of an existing structure(s) is necessary for the construction of a new structure. 5.408.1.3 Waste Stream Reduction Alternative The combined weight of new construction disposal that does not exceed 2 lbs/s.f. of building area may be deemed to meet the 50% minimum requirement as approved by the enforcing agency. 5.408.1.4 Documentation Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 5.408.1.1 through 5.408.1.3. The waste management plan shall be updated as necessary and shall be accessible during construction for examination by the enforcing agency. Notes: 1. Sample forms found in “A Guide to the California Green Building Standards Code (Nonresidential)” located at: http://www.bsc.ca.gov/CALGreen/default.htm may be used to assist in documenting compliance with the waste management plan. 2. Mixed construction and demolition debris (C&D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle). 5.408 2 Isolated jobsites The enforcing agency may make exceptions to the requirements of this section when jobsites are located in areas beyond the haul boundaries of the diversion facility. 5.408.3 Excavated soil and land clearing debris 100% of trees, stumps, rocks and associated vegetation and soils resulting primarily from land clearing shall be reused or recycled. For a phased project, such material may be stockpiled on site until the storage site is developed. Exception: Reuse, either on-or off-site, of vegetation or soil contaminated by disease or pest infestation. Notes: 1. If contamination by disease or pest infestation is suspected, contact the County Agricultural Commissioner and follow its direction for recycling or disposal of the material. (www.cdfa.ca.gov/exec/county/county_contacts.html) 2. For a map of known pest and/or disease quarantine zones, consult with the California Department of Food and Agriculture (www.cdfa.ca.gov) Division 5.4 – MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Building Maintenance and Operation) 5.410.1 Recycling by occupants Provide readily accessible areas that serve the entire building and are identified for the depositing, storage, and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics and metals. 5.410.1.1 Sample ordinance Space allocation for recycling areas shall comply with Chapter 18, Part 3, Division 30 of the Public Resources Code. Chapter 18 is known as the California Solid Waste Reuse and Recycling Access Act of 1991 (Act). Note: A sample ordinance for use by local agencies may be found in Appendix A of the document at the California Integrated Waste Management’s web site at: http://www.ciwmb.ca.gov/Publications/LocalAsst/31000012.doc . ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 5 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.4 – MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Building Maintenance and Operation) (Continued) 5.410.2 Commissioning For new buildings 10,000 square feet and over, building commissioning shall be included in the design and construction processes of the building project to verify that the building systems and components meet the owner’s or owner representative’s project requirements. Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of comparable size and complexity. Commissioning requirements shall include: 1. Owner’s Project Requirements. 2. Basis of Design. 3. Commissioning measures shown in the construction documents. 4. Commissioning Plan. 5. Functional Performance Testing. 6. Documentation & Training. 7. Commissioning Report. All building systems and components covered by Title 24, Part 6, as well as process equipment and controls, and renewable energy systems shall be included in the scope of the Commissioning Requirements. Exceptions: 1 .Dry storage warehouses of any size 2. Areas less than 10,000 square feet used for offices or other conditioned accessory spaces within dry storage warehouses 3. Tenant improvements under 10,000 square feet as described in Section 303.1.1. 5.410.2.1 Owner’s or Owner representative’s Project Requirements (OPR) The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following: 1. Environmental and Sustainability Goals. 2. Energy Efficiency Goals. 3. Indoor Environmental Quality Requirements. 4. Project program, including facility functions and hours of operation, and need for after hours operation. 5. Equipment and Systems Expectations. 6. Building Occupant and O&M Personnel Expectations. 5.410.2.2 Basis of Design (BOD) A written explanation of how the design of the building systems meets the OPR shall be completed at the design phase of the building project. The Basis of Design document shall cover the following systems: 1. Heating, Ventilation, Air Conditioning (HVAC) Systems and Controls. 2. Indoor Lighting System and Controls. 3. Water Heating System. 4. Renewable Energy Systems. 5. Landscape Irrigation Systems. 6. Water Reuse Systems. 5.410.2.3 Commissioning plan Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned and shall be started during the design phase of the building project. The Commissioning Plan shall include the following: 1. General Project Information. 2. Commissioning Goals. 3. Systems to be commissioned. Plans to test systems and components shall include: a. An explanation of the original design intent, b. Equipment and systems to be tested, including the extent of tests, c. Functions to be tested, d. Conditions under which the test shall be performed, e. Measurable criteria for acceptable performance. 4. Commissioning Team Information. 5. Commissioning process activities, schedules and responsibilities. Plans for the completion of commissioning shall be included. 5.410.2.4 Functional performance testing Functional performance tests shall demonstrate the correct installation and operation of each component, system, and system-to-system interface in accordance with the approved plans and specifications. Functional performance testing reports shall contain information addressing each of the building components tested, the testing methods utilized, and include any readings and adjustments made. 5.410.2.5 Documentation and training A Systems Manual and Systems Operations Training are required, including Occupational Safety and Health Act (OSHA) requirements in California Code of Regulations (CCR), Title 8, Section 5142, and other related regulations. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 6 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.4 – MATERIAL CONSERVATION & RESOURCE EFFICIENCY (Building Maintenance and Operation) (Continued) 5.410.2.5.1 Systems manual Documentation of the operational aspects of the building shall be completed within the Systems Manual and delivered to the building owner or representative and facilities operator. The Systems Manual shall include the following: 1. Site Information, including facility description, history and current requirements. 2. Site Contact Information. 3. Basic Operations & Maintenance, including general site operating procedures, basic troubleshooting, recommended maintenance requirements, site events log 4. Major Systems. 5. Site Equipment Inventory and Maintenance Notes. 6. A copy of verifications required by the enforcing agency or this code 7. Other resources and documentation if applicable. 5.410.2.5.2 Systems operations training A program for training of the appropriate maintenance staff for each equipment type and/or system shall be documented in the commissioning report and shall include the following: 1. System/Equipment overview (what it is, what it does and what other systems and/or equipment it interfaces with). 2. Review and demonstration of servicing/preventive maintenance. 3. Review of the information in the Systems Manual. 4. Review of the record drawings on the system/equipment. 5.410.2.6 Commissioning report A complete report of commissioning process activities undertaken through the design, construction and reporting recommendations for post-construction phases of the building project shall be completed and provided to the owner or representative. 5.410.4 Testing and adjustment Testing and adjusting of systems shall be required for buildings less than 10,000 square feet. 5.410.4.2 Systems Develop a written plan of procedures for testing and adjusting systems. Systems to be included for testing and adjusting shall include, as applicable to the project: 1. HVAC systems and controls 2. Indoor and outdoor lighting and controls 3. Water heating systems 4. Renewable energy systems 5. Landscape Irrigation Systems 6. Water Reuse Systems. 5.410.4.3 Procedures Perform testing and adjusting procedures in accordance with applicable standards on each system as determined by the enforcing agency. 5.410.4.3.1 HVAC balancing In addition to testing and adjusting, before a new space conditioning system serving a building or space is operated for normal use, balance the system in accordance with the procedures defined by the Testing Adjusting and Balancing Bureau National Standards; the National Environmental Balancing Bureau Procedural Standards; or Associated Air Balance Council National Standards or as approved by the enforcing agency. 5.410.4.4 Reporting After completion of testing, adjusting and balancing, provide a final report of testing signed by the individual responsible for performing these services. 5.410.4.5 Operation and maintenance (O & M) manual Provide the building owner or representative with detailed operating and maintenance instructions and copies of guaranties/warranties for each system. O & M instructions shall be consistent with OSHA requirements in CCR, Title 8, Section 5142, and other related regulations. 5.410.4.5.1 Inspection and reports Include a copy of all inspection verifications and reports required by the enforcing agency. Division 5.5 – ENVIRONMENTAL QUALITY (Fireplaces) 5.503.1 General Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed woodstove or pellet stove, and refer to residential requirements in the California Energy Code, Title 24, Part 6, Subchapter 7, Section 150. Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances. 5.503.1.1 Woodstoves Woodstoves and pellet stoves shall comply with US EPA Phase II emission limits. Division 5.5 – ENVIRONMENTAL QUALITY (Pollutant Control) 5.504.1.3 Temporary Ventilation The permanent HVAC system shall only be used during construction if necessary to condition the building within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2 1999, or an average efficiency of 30% based on ASHRAE 52.1 1992. Replace all filters immediately prior to occupancy. 5.504.3 Covering of duct openings and protection of mechanical equipment during construction At the time of rough installation and during storage on the construction site until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and debris which may enter the system. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 7 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.5 – ENVIRONMENTAL QUALITY (Pollutant Control) (Continued) 5.504.4 Finish material pollutant control Finish materials shall comply with Sections 5.504.4.1 through 5.504.4.4. 5.504.4.1 Adhesives, sealants and caulks Adhesives, sealants, and caulks used on the project shall meet the requirements of the following standards. 1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers, and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable, or SCAQMD Rule 1168 VOC limits, as shown in Tables 5.504.4.1 and 5.504.4.2. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene, and trichloroethylene), except for aerosol products as specified in subsection 2, below. 2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507. Note: Title 17 may be found at http://ccr.oal.ca.gov/ . 5.504.4.5.3 Documentatio n Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following. 1. Product certifications and specifications. 2. Chain of custody certifications. 3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.) 4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269 or European 636 3S standards. 5. Other methods acceptable to the enforcing agency. 5.504.4.3 Paints and coatings Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Coatings Suggested Control Measure, as shown in Table 5.504.4.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 5.504.4.3, shall be determined by classifying the coating as a Flat, Nonflat, or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure, and the corresponding Flat, Nonflat, or Nonflat-High Gloss VOC limit in Table 5.504.4.3 shall apply. 5.504.4.3.1 Aerosol paints and coatings Aerosol paints and coatings shall meet the Product-Weighted MIR Limits for ROC in section 94522(a)(3) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in sections 94522(c)(2) and of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality management District additionally comply with the percent VOC by weight of product limits of Regulation 8 Rule 49. 5.504.4.3.2 Verification Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following: 1. Manufacturers product specification. 2. Field verification of on-site product containers. 5.504.4.4 Carpet systems All carpet installed in the building interior shall meet the testing and product requirements of one of the following: 1. Carpet and Rug Institute’s Green Label Plus Program 2. California Department of Public Health Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350). 3. NSF/ANSI 140 at the Gold level or higher. 4. Scientific Certifications Systems Sustainable Choice. 5.504.4.4.1 Carpet cushion All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute Green Label program. 5.504.4.4.2 Carpet adhesive All carpet adhesive shall meet the requirements of Table 5.504.4.1. 5.504.4.5 Composite wood products Hardwood plywood, particleboard, and medium density fiberboard composite wood products used on the interior or exterior of the building shall meet the requirements for formaldehyde as specified in ARB’s Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 5.504.4.5 Table not shown – refer to Code 5.504.4.5.1 Early Compliance Reserved ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 8 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.5 – ENVIRONMENTAL QUALITY (Pollutant Control) (Continued) 5.504.4.6 Resilient flooring systems For 50 percent of floor area receiving resilient flooring, install resilient flooring complying with the VOC-emission limits defined in the 2009 Collaborative for High Performance Schools (CHPS) criteria and listed on its High Performance Products Database; products compliant with CHPS criteria certified under the Greenguard Children & Schools program; certified under the Resilient Floor Covering Institute (RFCI) FloorScore program; or meet California Department of Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.) [DSA-SS] Documentation shall be provided that verifies that finish materials are certified to meet the pollutant emission limits. 5.504.4.6.1 Verification of compliance Documentation shall be provided verifying that resilient flooring materials meet the pollutant emission limits. Notes: 1. CHPS Low-emitting Materials List may be found at or http://www.chps.net/dev/Drupal/node/381 . 2. Products certified under the FloorScore program may be found at: http://www.rfci.com/int_FS- ProdCert.htm Products certified under the Greenguard Children & Schools program and compliant with CHPS criteria may be found at: http://www.greenguard.org/Default.aspx?tabid=135. 5.504.5.3 Filters In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 8. MERV 8 filters shall be installed prior to occupancy, and recommendations for maintenance with filters of the same value shall be included in the operation and maintenance manual. Exception: A MERV-1 filter shall be allowed for return air only or return with prefiltered outside air if the filter is of a re-usable, non-disposable type, and the fan energy use of that air delivery system is 0.4W/cfm or less at design airflow. 5.504.7 Environmental tobacco smoke (ETS) control Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building as already prohibited by other laws or regulations; or as enforced by ordinances, regulations, or policies of any city, county, city and county, California Community College, campus of the California State University, or campus of the University of California, whichever are more stringent. When ordinances, regulations, or policies are not in place, post signage to inform building occupants of the prohibitions. Division 5.5 – ENVIRONMENTAL QUALITY (Indoor Moisture Control) 5.505.1 Indoor moisture control Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures not applicable to low-rise residential occupancies, see Section 5.407.2 of this code. Division 5.5 – ENVIRONMENTAL QUALITY (Indoor Air Quality) 5.506.1 Outside air delivery For mechanically or naturally ventilated spaces in buildings, meet the minimum requirements of Section 121 (Requirements For Ventilation) of the California Energy Code, CCR, Title 24, Part 6, or the applicable local code, whichever is more stringent, and Chapter 4 of CCR, Title 8. 5.506.2 Carbon dioxide (CO2) monitoring For buildings equipped with demand control ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements of the current edition of the California Energy Code, CCR, Title 24, Part 6, Section 121(c). Division 5.5 – ENVIRONMENTAL QUALITY (Environmental Comfort) 5.507.4 Acoustical control Employ building assemblies and components with Sound Transmission Class (STC) values determined in accordance with ASTM E90 and ASTM E413 or Outdoor-Indoor Sound Transmission Class (OITC) determined in accordance with ASTM E1332, using either the prescriptive or performance method in Section 5.507.4.1 or 5.507.4.2. Exception: Buildings with few or no occupants or where occupants are not likely to be affected by exterior noise, as determined by the enforcement authority, such as factories, stadiums, storage, enclosed parking structures, and utility buildings. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 9 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.5 – ENVIRONMENTAL QUALITY (Environmental Comfort) (Continued) 5.507.4.1 Exterior noise transmission, prescriptive method Wall and roof-ceiling assemblies exposed to the noise source making up the building envelope shall meet a composite STC rating of at least 50 or a composite OITC rating of no less than 40, with exterior windows of a minimum STC of 40 or OITC of 30 in the following locations: 1. Within the 65 CNEL noise contour of an airport Exceptions: 1. Ldn or CNEL for military airports shall be determined by the facility Air Installation Compatible Land Use Zone (AICUZ) plan. 2. Ldn or CNEL for other airports and heliports for which a land use plan has not been developed shall be determined by the local general plan noise element. 2. Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or fixed-guideway noise source as determined by the Noise Element of the General Plan 5.507.4.1.1 Noise exposure where noise contours are not readily available Buildings exposed to a noise level of 65 dB Leq-1-hr during any hour of operation shall have exterior wall and roof-ceiling assemblies exposed to the noise source meeting a composite STC rating of at least 45 (or OITC 35), with exterior windows of a minimum STC of 40 (or OITC 30). 5.507.4.2 Performance Method For buildings located as defined in Sections A5.507.4.1 or A5.507.4.1.1, wall and roof-ceiling assemblies exposed to the noise source making up the building envelope shall be constructed to provide an interior noise environment attributable to exterior sources that does not exceed an hourly equivalent noise level (Leq-1Hr) of 50 dBA in occupied areas during any hour of operation. 5.507.4.2.1 Site features Exterior features such as sound walls or earth berms may be utilized as appropriate to the project to mitigate sound migration to the interior. 5.507.4.2.2 Documentatio n of compliance An acoustical analysis documenting complying interior sound levels shall be prepared by personnel approved by the architect or engineer of record. 5.507.4.3 Interior sound transmission Wall and floor-ceiling assemblies separating tenant spaces and tenant spaces and public places shall have an STC of at least 40. Note: Examples of assemblies and their various STC ratings may be found at the California Office of Noise Control: http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf . Division 5.5 – ENVIRONMENTAL QUALITY (Outdoor Air Quality) 5.508.1 Ozone depletion and greenhouse gas reductions Installations of HVAC, refrigeration, and fire suppression equipment shall comply with Sections 5.508.1.1 and 5.508.1.2. 5.508.1.1 Chlorofluoroc arbons (CFCs.) Install HVAC, refrigeration and fire suppression equipment that do not contain CFCs. 5.508.1.2 Halons Install HVAC, refrigeration and fire suppression equipment that do not contain Halons. DIVISION 5.7 – NEW - ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS 5.701.1 Scope For those occupancies subject to section 103 of this code, the provisions of this division shall apply to the planning, design, operation, construction, use and occupancy of additions to buildings or structures unless otherwise indicated in this code. The provisions of this Division shall only apply to the portions of the building being added or altered within the scope of the permitted work. Compliance for additions and alterations is required on or after the dates shown in Table 5.701 TABLE 5.701 Effective date of compliance Square footage of addition Permit valuation or estimated construction cost of alteration July 1, 2012 2000 $500,000 Effective date of the 2013 California Building Standards Code January 1, 2014 1000 $200,000 Notes: 1) The effective date of the 2013 California Building Standards Code is currently projected to be January 1, 2014. 2) This division does not apply to additions and alterations of qualified historical buildings. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 10 of 17 SECTION CREDIT REQUIREMENTS PC INSP DIVISION 5.7 – NEW - ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Continued) 5.702.1 Definitions Unless otherwise stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this division. Refer also to definitions in Chapter 2 of this code. ADDITION. An extension or increase in floor area of an existing building or structure. ALTERATION OR ALTER. Any construction or renovation to an existing structure other than repair for the purpose of maintenance or addition. ARB (CARB). The California Air Resources Board. Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Green Building) 5.703.1 Scope Building additions and alterations shall be designed to include the green building measures specified as mandatory in the application checklists for alterations or additions contained in this code. 5.703.2 Phased projects For shell buildings and others constructed for future tenant improvements, only those code measures relevant to the building components and systems considered to be new construction (or newly constructed) shall apply. 5.703.2.1 Tenant improvements The provisions of this code shall apply to the initial tenant or occupant improvements to a project and to subsequent tenant improvements subject to Section 5.701.1. Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Site Development) 5.710.6.1 Storm water pollution prevention Additions that disturb soil of less than one acre shall prevent the pollution of storm water runoff from the construction activities through one or more of the following measures: 5.710.6.1.1 Local ordinance Comply with a lawfully enacted storm water management and/or erosion control ordinance. 5.710.6.1.2 Best management practices (BMP) Prevent the loss of soil through wind or water erosion by implementing an effective combination of erosion and sediment control and good housekeeping BMP. 1. Soil loss BMP that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a. Scheduling construction activity b. Preservation of natural features, vegetation and soil c. Drainage swales or lined ditches to control storm water flow d. Mulching or hydro seeding to stabilize disturbed soils e. Erosion control to protect slopes f. Protection of storm drain inlets (gravel bags or catch basin inserts) g. Perimeter sediment control (perimeter silt fence, fiber rolls) h. Sediment trap or sediment basin to retain sediment on site i. Stabilized construction exits j. Wind erosion control k. Other soil loss BMP acceptable to the enforcing agency 2. Good housekeeping BMP to manage construction equipment, materials, and wastes that should be considered for implementation as appropriate for each project include, but are not limited to, the following: a. Material handling and waste management b. Building materials stockpile management c. Management of washout areas (concrete, paints, stucco, etc.) d. Control of vehicle/equipment fueling to contractor’s staging area e. Vehicle and equipment cleaning performed off site f. Spill prevention and control g. Other housekeeping BMP acceptable to the enforcing agency 5.710.6.2 Bicycle parking Comply with Sections 5.710.6.2.1 and 5.710.6.2.2; or meet the applicable local ordinance, whichever is stricter. 5.710.6.2.1 Short-term bicycle parking If the project is anticipated to generate visitor traffic and adds 10 or more vehicular parking spaces, provide permanently anchored bicycle racks within 200 feet of the visitors’ entrance, readily visible to passers-by, for 5% of the additional visitor motorized vehicle parking capacity, with a minimum of one two-bike capacity rack. 5.710.6.2.2 Long-term bicycle parking For buildings with over 10 tenant-occupants that add 10 or more vehicular parking spaces, provide secure bicycle parking for 5% of additional motorized vehicle parking capacity, with a minimum of one space. Acceptable parking facilities shall be convenient from the street and may include: 1. Covered, lockable enclosures with permanently anchored racks for bicycles; 2. Lockable bicycle rooms with permanently anchored racks; and 3. Lockable, permanently anchored bicycle lockers. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 11 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Site Development) (Continued) 5.710.6.3 Designated parking For projects that add 10 or more vehicular parking spaces, provide designated parking for any combination of low-emitting, fuel efficient, and carpool/van pool vehicles as shown in Table 5.106.2.2 of Division 5.1 based on the number of additional spaces. 5.710.6.3.1 Parking stall marking Paint, in the paint used for stall striping, the following characters such that the lower edge of the last word aligns with the end of the stall striping and is visible beneath a parked vehicle: CLEAN AIR/ VANPOOL/EV Note: Vehicles bearing Clean Air Vehicle stickers from expired HOV lane programs may be considered eligible for designated parking spaces. 5.710.6.6 Grading and Paving Construction plans shall indicate how site grading or a drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following: 1. Swales 2. Water collection and disposal systems 3. French drains 4. Water retention gardens 5. Other water measures which keep surface water away from buildings and aid in groundwater recharge Exception: Additions and alterations not altering the drainage path. DIVISION 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Water Efficiency & Conservation) 5.712.3.1 Meters Separate sub meters or metering devices shall be installed for the uses described in Sections 5.712.3.1.1 and 5.713.3.1.2. 5.712.3.1.1 Additions to existing buildings in excess of 50,000 square feet (4645 m2) Separate sub meters shall be installed as follows: 1. For each individual leased, rented, or other tenant space within the building projected to consume more than 100 gal/day (380 L/day), including, but not limited to, spaces used for laundry or cleaners, restaurant or food service, medical or dental office, laboratory, or beauty salon or barber shop. 2. Where meters for individual building tenants are unfeasible, for water supplied to the following a. Makeup water for cooling towers where flow through is greater than 500 gpm (30 L/s) b. Makeup water for evaporative coolers greater than 6 gpm (0.04 L/s) c. Steam and hot-water boilers with energy input more than 500,000 Btu/h (147 kW) 5.712.3.1.2 Excess consumption Any addition or added space within an addition that is projected to consume more than 1,000 gal/day (3800 L/day). 5.712.3.2 20 Percent Savings A schedule of newly installed plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the addition or area of alteration to the building by 20% shall be provided. The reduction shall be based on the maximum allowable water use per plumbing fixture and fittings as required by the California Building Standards Code. The 20% reduction in potable water use shall be demonstrated by one of the following methods. [Balance of subsections are identical to those in Division 5.3] 5.712.3.3 Multiple showerheads serving one shower When a shower is served by more than one newly installed showerhead, the combined flow rate of all the showerheads controlled by a single valve shall not exceed the maximum flow rate at ≥20 percent reduction contained in Table 5.303.2.2 or the shower shall be designed to only allow one showerhead to be in operation at a time. Exception: The maximum flow rate for shower heads when using the performance method specified in Section 5.303.2.1, Item 2 is 2.5 gpm @ 80 psi. 5.712.3.5 Plumbing fixtures and fittings Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall meet the standards referenced in Table 5.503.6. [Table 5.303.6 is not shown for clarity, but referenced standard ASME 112.18.1/CSA B125.1 was added in the table for showerheads with a maximum flow rate of 2.5 gal (9.5l.)/min.] 5.712.4.1 Water budget A water budget shall be developed for landscape irrigation use installed in conjunction with addition or alteration that conforms to the local water efficient landscape ordinance or to the California Department of Water Resources Model Water Efficient Landscape Ordinance where no local ordinance is applicable. Note: Prescriptive measures to assist in compliance with the water budget are listed in Sections 492.5 through 492.8, 492.10 and 492.11 of the ordinance, which may be found at: http://www.owue.water.ca.gov/landscape/ord/ord.cfm ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 12 of 17 SECTION CREDIT REQUIREMENTS PC INSP DIVISION 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Water Efficiency & Conservation) (Continued) 5.712.4.2 Outdoor potable water use For building addition or alteration requiring upgraded water service for landscaped areas of at least 1000 square feet but not more than 5000 square feet (the level at which Water Code §535 applies), separate sub meters or metering devices shall be installed for outdoor potable water use. 5.712.4.3 Irrigation design In building addition or alteration with at least 1000 square feet but not more than 2500 square feet of cumulative landscaped area (the level at which the MLO applies), install irrigation controllers and sensors which include the following criteria, and meet manufacturer’s recommendations. Exception: New irrigation controllers are not required when existing irrigation controllers have sufficient capacity to serve the new landscaped area. [Balance of subsections are unchanged from those in Division 5.3] 5.712.4.3.1 Irrigation controllers Automatic irrigation system controllers installed at the time of final inspection shall comply with the following: 1. Controllers shall be weather- or soil moisture-based controllers that automatically adjust irrigation in response to changes in plants’ needs as weather conditions change. 2. Weather-based controllers without integral rain sensors or communication systems that account for local rainfall shall have a separate wired or wireless rain sensor which connects or communicates with the controller(s). Soil moisture-based controllers are not required to have rain sensor input. Note: More information regarding irrigation controller function and specifications is available from the Irrigation Association. Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Material Conservation & Resource Efficiency) 5.713.7.1 Weather protection Provide a weather-resistant exterior wall and foundation envelope as required by California Building Code Section 1403.2 (Weather Protection) and California Energy Code Section 150, (Mandatory Features and Devices), manufacturer’s installation instructions, or local ordinance, whichever is more stringent. 5.713.7.2 Moisture control Employ moisture control measures by the following methods. 5.713.7.2.1 Sprinklers Design and maintain landscape irrigation systems to prevent spray on structures. 5.713.7.2.2 Entries and openings Design exterior entries and/or openings subject to foot traffic or wind-driven rain to prevent water intrusion into buildings. Notes: 1. Use features such as overhangs and recesses, and flashings integrated with a drainage plane. 2. Use non-absorbent floor and wall finishes within at least two feet around and perpendicular to such openings. 5.713.8.1 Construction waste management For additions and remodels recycle and/or salvage for reuse a minimum of 50 percent of the non- hazardous construction waste in accordance with Section 5.713.8.1.1 or 5.713.8.1.2; or meet a local construction and demolition waste management ordinance, whichever is more stringent. [The provision in Division 5.4 for a waste stream alternative is eliminated from this subsection, with the balance of subsections unchanged from those in Division 5.4] 5.713.8.1.1 Construction waste management plan Where a local jurisdiction does not have a construction and demolition waste management ordinance that is more stringent, submit a construction waste management plan that: 1. Identifies the construction waste materials to be diverted from disposal by efficient usage, recycling, reuse on the project, or salvage for future use or sale. 2. Determines if construction waste materials will be sorted on-site (source-separated) or bulk mixed (single stream). 3. Identifies diversion facilities where construction waste material collected will be taken. 4. Specifies that the amount of construction waste materials diverted shall be calculated by weight or volume, but not by both. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 13 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Material Conservation & Resource Efficiency) (Continued) 5.713.8.1.2 Waste management company Utilize a waste management company that can provide verifiable documentation that the percentage of construction waste material diverted from the landfill complies with this section. Note: The owner or contractor shall make the determination if the construction waste material will be diverted by a waste management company. Exceptions to 5.713.8.1.1 and 5.713.8.1.2: 1. Excavated soil and land-clearing debris 2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist. 3. Demolition waste meeting local ordinance or calculated in consideration of local recycling facilities and markets, where demolition of an existing structure(s) is necessary for the construction of a new structure. 5.713.8.1.3 Documentatio n Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 5.713.8.1.1, Items 1 through 4. The waste management plan shall be updated as necessary and shall be accessible during construction for examination by the enforcing agency. 5.713.8.2 Isolated jobsites The enforcing agency may make exceptions to the requirements of this section when jobsites are located in areas beyond the haul boundaries of the diversion facility. 5.713.8.3 Excavated soil and land clearing debris 100 percent of trees, stumps, rocks and associated vegetation and soils resulting primarily from land clearing shall be reused or recycled. For a phased project, such material may be stockpiled on site until the storage site is developed. Exception: Reuse, either on-or off-site, of vegetation or soil contaminated by disease or pest infestation. Notes: 3. If contamination by disease or pest infestation is suspected, contact the County Agricultural Commissioner and follow its direction for recycling or disposal of the material. (www.cdfa.ca.gov/exec/county/county_contacts.html) 4. For a map of known pest and/or disease quarantine zones, consult with the California Department of Food and Agriculture (www.cdfa.ca.gov) 5.713.10.1 Recycling by occupants If not provided on the existing site and where site conditions permit, provide readily accessible areas that serve the entire building and are identified for the depositing, storage, and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics and metals in accordance with one of the following: 1. For additions or alterations by an owner or a tenant conducted within a 12-month period under single or multiple permits resulting in an increase of 30% or more in floor area 2. For additions or alterations by an owner or a tenant for which multiple permits are applied within a 12-month period resulting in an increase of 30% or more in floor area 3. As required by a lawfully enacted local recycling ordinance, if more restrictive. [Balance of subsections are identical to those in Division 5.4] 5.713.10.1.1 Sample ordinance Space allocation for recycling areas shall comply with Chapter 18, Part 3, Division 30 of the Public Resources Code. Chapter 18 is known as the California Solid Waste Reuse and Recycling Access Act of 19991 (Act). Note: A sample ordinance for use by local agencies may be found in Appendix A of the document at the CalRecycle’s website. 5.713.10.4 Testing and adjusting Testing and adjusting of new systems installed to serve an addition or alteration subject to Section 5.701.1 shall be required. [Balance of subsections are unchanged from those in Division 5.4] 5.713.10.4.2 Systems Develop a written plan of procedures for testing and adjusting systems. Systems to be included for testing and adjusting shall include, as applicable to the project: 1. HVAC systems and controls 2. Indoor and outdoor lighting and controls 3. Water heating systems 4. Renewable energy systems 5. Landscape irrigation systems 6. Water reuse systems 5.713.10.4.3 Procedures Perform testing and adjusting procedures in accordance with manufacturer’s specifications and applicable standards on each system. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 14 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 –ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Material Conservation & Resource Efficiency) (Continued) 5.713.10.4.3.1 HVAC balancing In addition to testing and adjusting, before a new space conditioning system serving a building or space is operated for normal use, balance the system in accordance with the procedures defined by the Testing Adjusting and Balancing Bureau National Standards; the National Environmental Balancing Bureau Procedural Standards; or Associated Air Balance Council National Standards or as approved by the enforcing agency. 5.713.10.4.4 Reporting After completion of testing, adjusting and balancing, provide a final report of testing signed by the individual responsible for performing these services. 5.713.10.4.5 Operation and maintenance (O&M) manual Provide the building owner or representative with detailed operating and maintenance instructions and copies of guaranties/warranties for each system. O & M instructions shall be consistent with OSHA requirements in CCR, Title 8, Section 5142, and other related regulations. 5.713.10.4.5.1 Inspections and reports Include a copy of all inspection verifications and reports required by the enforcing agency. Division 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Environmental Quality) 5.714.3.1 General Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed woodstove or pellet stove, and refer to residential requirements in the California Energy Code, Title 24, Part 6, Subchapter 7, Section 150. Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances. 5.714.3.1.1 Woodstoves Woodstoves and pellet stoves shall comply with U.S. EPA Phase II emission limits. 5.714.4.1 Temporary ventilation The permanent HVAC system shall only be used during construction if necessary to condition the building within the required temperature range for material and equipment installation. If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2 1999, or an average efficiency of 30% based on ASHRAE 52.1 1992. Replace all filters immediately prior to occupancy. 5.714.4.3 Covering of duct openings and protection of mechanical equipment during construction At the time of rough installation and during storage on the construction site until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and debris which may enter the system. 5.714.4.4 Finish material pollutant control Finish materials shall comply with Sections 5.714.4.4.1 through 5.714.4.4.6 Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.) 5.714.4.4.1 Adhesives, sealants, and caulks Adhesives, sealants, and caulks. Adhesives, sealants, and caulks used on the project shall meet the requirements of the following standards: 1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable, or SCAQMD Rule 1168 VOC limits, as shown in Tables 5.504.4.1 and 5.504.4.2 in Division 5.5. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene, and trichloroethylene), except for aerosol products as specified in subsection 2, below. 2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507. 5.714.4.4.3 Paints and coatings Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Coatings Suggested Control Measure, as shown in Table 5.504.4.3 in Division 5.5, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 5.504.4.3, shall be determined by classifying the coating as a Flat, Nonflat, or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board Suggested Control Measure, and the corresponding Flat, Nonflat, or Nonflat- High Gloss VOC limit in Table 5.504.4.3 shall apply. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 15 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Environmental Quality) (Continued) 5.714.4.4.3.1 Aerosol paints and coatings Aerosol paints and coatings shall meet the Product-Weighted MIR Limits for ROC in section 94522(a)(3) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in sections 94522(c)(2) and of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8 Rule 49. 5.714.4.4.3.2 Verification Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following: 1. Manufacturers product specification 2. Field verification of on-site product containers. 5.714.4.4.4 Carpet Systems All carpet installed in the building interior shall meet the testing and product requirements of one of the following: 1. Carpet and Rug Institute’s Green Label Plus Program. 2. California Department of Public Health Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350). 3. NSF/ANSI 140 at the Gold level or higher. 4. Scientific Certifications Systems Sustainable Choice. 5.714.4.4.4.1 Carpet cushion All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute’s Green Label program. 5.714.4.4.4.2 Carpet adhesive All carpet adhesive shall meet the requirements of Table 5.504.4.1 in Division 5.5. 5.714.4.4.5 Composite wood products Hardwood plywood, particleboard, and medium density fiberboard composite wood products used on the interior or exterior of the building shall meet the requirements for formaldehyde as specified in CARB’s Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 5.504.4.5. Table not shown – refer to Code 5.714.4.4.5.2 Documentatio n Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following: 1. Product certifications and specifications 2. Chain of custody certifications 3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.) 4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269 or European 636 3S standards. 5. Other methods acceptable to the enforcing agency. 5.714.4.4.6 Resilient flooring systems For 50 percent of floor area receiving resilient flooring, install resilient flooring complying with the VOC-emission limits defined in the 2009 Collaborative for High Performance Schools (CHPS) criteria and listed on its High Performance Products Database; products compliant with CHPS criteria certified under the Greenguard Children & Schools program; certified under the Resilient Floor Covering Institute (RFCI) FloorScore program; or meet California Department of Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.) 5.714.4.4.6.1 Verification of compliance Documentation shall be provided verifying that resilient flooring materials meet the pollutant emission limits. 5.714.4.5 Hazardous particulates and chemical pollutants Minimize and control pollutant entry into buildings and cross-contamination of regularly occupied areas. 5.714.4.5.3 Filters In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 8. MERV 8 filters shall be installed prior to occupancy, and recommendations for maintenance with filters of the same value shall be included in the operation and maintenance manual. Exception: A MERV-1 filter shall be allowed for return air only or return with prefiltered outside air if the filter is of a re-usable, non-disposable type, and the fan energy use of that air delivery system is 0.4W/cfm or less at design airflow. ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 16 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Environmental Quality) (Continued) 5.714.4.7 Environmental tobacco smoke (ETS) control Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building as already prohibited by other laws or regulations; or as enforced by ordinances, regulations, or policies of any city, county, city and county, California Community College, campus of the California State University, or campus of the University of California, whichever are more stringent. When ordinances, regulations, or policies are not in place, post signage to inform building occupants of the prohibitions. 5.714.5.1 Indoor moisture control Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures not applicable to low-rise residential occupancies, see Section 5.407.2 of this code. 5. 714.6.1 Outside air delivery For mechanically or naturally ventilated spaces in buildings, meet the minimum requirements of Section 121 (Requirements For Ventilation) of the 2010 California Energy Code, or the applicable local code, whichever is more stringent, and Division 1, Chapter 4 of CCR, Title 8. 5.714.6.2 Carbon dioxide (CO2) monitoring. [BSC] For buildings equipped with demand control ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements of 2010 California Energy Code, Section 121(c). 5.714.7.1 Acoustical control Employ building assemblies and components with Sound Transmission Class (STC) values determined in accordance with ASTM E90 and ASTM E413 or Outdoor-Indoor Sound Transmission Class (OITC) determined in accordance with ASTM E1332 using either the prescriptive or performance method in Section 5.714.1.1 or 5.714.1.2. Exception: Buildings with few or no occupants or where occupants are not likely to be affected by exterior noise, as determined by the enforcement authority, such as factories, stadiums, storage, enclosed parking structures, and utility buildings. 5.714.7.1.1 Exterior noise transmission, prescriptive method Wall and roof-ceiling assemblies exposed to the noise source making up the building addition or altered envelope shall meet a composite STC rating of at least 50 or a composite OITC rating of no less than 40, with exterior windows of a minimum STC of 40 or OITC of 30 in the following building locations: 1. Within the 65 CNEL noise contour of an airport Exceptions: 1. Ldn or CNEL for military airports shall be determined by the facility Air Installation Compatible Land Use Zone (AICUZ) plan. 2. Ldn or CNEL for other airports and heliports for which a land use plan has not been developed shall be determined by the local general plan noise element. 2. Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or fixed-guide way noise source as determined by the Noise Element of the General Plan. 5.714.7.1.1.1 Noise exposure where noise contours are not readily available Buildings exposed to a noise level of 65 dB (Leq-1Hr) during any hour of operation shall have building addition or alteration exterior wall and roof-ceiling assemblies exposed to the noise source meeting a composite STC rating of at least 45 (or OITC 35), with exterior windows of a minimum STC of 40 (or OITC 30). 5.714.7.1.2 Performance method For buildings located as defined in Sections A5.714.7.1.1 or A5.714.7.1.1.1, wall and roof-ceiling assemblies exposed to the noise source making up the building addition or altered envelope shall be constructed to provide an interior noise environment attributable to exterior sources that does not exceed an hourly equivalent noise level (Leq-1Hr) of 50 dBA in occupied areas during any hour of operation. 5.714.4.1.2.1 Site features Exterior features such as sound walls or earth berms may be utilized as appropriate to the addition or alteration project to mitigate sound migration to the interior. 5.714.7.1.2.2 Documentatio n of compliance An acoustical analysis documenting complying interior sound levels shall be prepared by personnel approved by the architect or engineer of record 5.714.7.1.3 Interior sound transmission Wall and floor-ceiling assemblies separating tenant spaces and tenant spaces and public places in additions and in alterations modifying existing partitions or installing new partitions shall have an STC of at least 40. Note: Examples of assemblies and their various STC ratings may be found at the California Office of Noise Control: http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf . ---PAGE BREAK--- NON-RESIDENTIAL MANDATORY MEASURES CHECKLIST Page 17 of 17 SECTION CREDIT REQUIREMENTS PC INSP Division 5.7 – ADDITIONS AND ALTERATIONS TO EXISTING NONRESIDENTIAL BUILDINGS (Environmental Quality) (Continued) 5.714.8.1 Ozone depletion and greenhouse gas reductions. Installations of HVAC, refrigeration and fire suppression equipment shall comply with Sections 5.508.1.1 and 5.508.1.2. 5.714.8.1.1 Chlorofluoroca rbons (CFCs.) Install HVAC, refrigeration and fire suppression equipment that do not contain CFCs. 5.714.8.1.2 Halons. Install HVAC, refrigeration and fire suppression equipment that do not contain Halons. For new buildings 10,000 square feet and over, building commissioning shall be included in the design and construction processes of the building project to verify that the building systems and components meet the owner’s or owner representative’s project requirements. Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of comparable size and complexity. Building Commissioning is a systematic quality assurance process that spans the entire design and construction process, including verifying and documenting that building systems and components are planned, designed, installed, tested, operated, and maintained to meet the owner’s project requirements.