Full Text
FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT T&D CONSTRUCTION STANDARDS SUB MAINT NEW SHEET NEW SHEET N/A N/A 6.9KV SINGLE PHASE FUSE CABINET 34" x 40" PAD INSTALLATION CU1600-61 REV4 4 01-15 1 2 CU 1600-61 18" 40" 11" 5" 4" 34" 5 712" 1112" 17"x30" PULLBOX INVERTED 2 5"x1112" CLEAR OPENING IN PAD 12" THREADED INSERTS W/BOLTS 17"x30" INVERTED PULL BOX FINISH GRADE 4" 1 2" PLAN VIEW 6" 3"-4" SEPARATION LOAD LINE 3 4 1 ROCK BASE SEE CO 780 SCOPE: THIS STANDARD SHOWS REQUIREMENTS FOR EASEMENT AND CLEARANCE AND INSTALLATION OF POLYMER/CONCRETE PAD FOR 6.9kV SINGLE PHASE PAD MOUNTED FUSE CABINET. 3' 8'10" EASEMENT 34" 14'3" EASEMENT 8' 40" 3' 3' EASEMENT AND CLEARANCE REQUIREMENT 2 INSTALLATION & GROUNDING DETAIL LOAD SIDE CONDUIT (4"C MAX.) LINE SIDE CONDUIT (4"C MAX.) TRENCH BOTTOM ---PAGE BREAK--- FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : APPROVALS CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT T&D CONSTRUCTION STANDARDS SUB MAINT NEW SHEET NEW SHEET N/A N/A 6.9KV SINGLE PHASE FUSE CABINET 34" x 40" PAD INSTALLATION CU1600-61 REV4 4 01-15 2 2 CU 1600-61 ITEM QTY DESCRIPTION 1 1 PAD, FUSE CABINET 34" X 40" 2 WIRE, #4 B.C. SOLID SOFT DRAWN 3 ROD, GROUND 5/8" X 8' COPPERWELD 4 CLAMPS, GROUND MATERIAL LIST ANAHEIM PART NO. 446150 AS REQ'D. 2 2 SEE BELOW 547005 568075 17" X 30" PULL BOX 1 5 486300 A. GROUND RODS TO CLEAR ALL CONDUITS IN UNDISTRUBED SOIL, PER CO782 B. LOCATE CONDUITS MAX.) AS SHOWN AND WITHIN PULL BOX OPENING. (NOTE LINE AND LOAD SIDE POSITIONS). C. INSTALL TEMPORARY CONDUIT PLUGS IN ALL CONDUITS PER CU 16OO-96H. D. BACKFILL AND COMPACT SOIL TO 95%, INSTALL 6" OF 3 4" ROCK BASE. E. INSTALL AND LEVEL PAD, BACKFILL TO 2" BELOW PAD TOP. F. FILL PULL BOX OPENING AROUND CONDUITS WITH 2" LAYER OF 3 4" ROCK FOR WEED AND RODENT CONTROL. G. MAINTAIN 8 FEET MIN. WORKING CLEARANCE IN FRONT OF PAD AND 3' CLEARANCE IN SIDES AND BACK. H. RETAINING WALLS PER CU 16OO-6. J. PROTECTIVE POSTS PER CU 16OO-9. K. PAD COMES COMPLETE WITH 2 NON-CORROSIVE 12" THREADED INSERTS (CAST IN PLACE) AND 12" HEX HEAD BOLTS INSTALLED FOR CABINET HOLD DOWN. L. INSTALL FUSE CABINET PER CU 16OO-6O. M. INSTALL INVERTED 17"X30" PULL BOX BELOW PAD SLOT PER CU 1500-1A. RETURN UN-USED TOP TO STOCK NOTES: MATERIAL SIZE UTILITY VAULT CO. ANAHEIM PART NO. 34" X 4O" POLYMER - - - PP1P-3440-90001 FUSE CABINET PAD JENSEN NEWBASIS COMPATIBLE UNIT W4CUBARE-SD PB17X30POLY