Full Text
FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : NEW SHEET NEW SHEET APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS SYS PLN MGR SUB MAINT SR ELEC ENG. 12KV PAD MOUNTED CAPACITOR CABINET INSTALLATION REQUIREMENTS CU 1600-2 REV 6 6 07-21 1 2 CU 1600-2 SCOPE: THIS STANDARD SHOWS PAD SIZE AND INSTALLATION REQUIREMENTS FOR 12KV PAD MOUNTED CAPACITOR CABINET. 95% COMPACTED SOIL 3" " L " 6' MIN. 3" 22" " W " " T " (SEE NOTE A) (SEE NOTE B) 36" MIN. 3'-0" 3'-11" 3'-6" GRADE GRADE 7" 13" 1 2 3 6 5 4 24" MIN. 18" SMOOTH LEVEL FINISH 3y" (TYP.) ALL AROUND (SEE NOTE A) 1" DRAFT (TYP.) PRECAST ONLY UNISTRUT (PRECAST ONLY) PAD OPENING (SEE NOTE B) LOCATE 2 - 2" CONDUITS PER DIMENSIONS SHOWN 1 - 4" CONDUIT PER CU 1600-25 FOR PRIMARY CABLE (SEE NOTE C) 1y" (TYP.) (SEE NOTE A) 2 - 2" PVC CONDUITS FOR TELECOM./CONTROL SYSTEM. (SEE NOTE C) 1" DRAFT (TYP.) PRECAST ONLY FIELD POURED PRECAST PLAN VIEW SECTION A-A PLACE PRECAST PAD ON 6" OF i" CRUSHED ROCK A A TEXT MANUFACTURER STYLE ANAHEIM PART NO. FIELD POURED - 96" 80" 6" - JENSEN PD7294-T6-11 94" 72" 6" - OLD CASTLE ANA 7294-08 PAD 94" 72" 8" - ---PAGE BREAK--- FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : NEW SHEET NEW SHEET APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS SYS PLN MGR SUB MAINT SR ELEC ENG. 12KV PAD MOUNTED CAPACITOR CABINET INSTALLATION REQUIREMENTS CU 1600-2 REV 6 6 07-21 2 2 CU 1600-2 MATERIAL LIST NOTES: A. POURED PAD: PAD SIZE, PER TABLE. CONCRETE TO BE 3000 PSI (MINIMUM) AT 28 DAYS. REINFORCING STEEL TO BE NO. 4 BARS INSTALLED IN DOUBLE NET. PERIMETER BARS TO BE CONTINUOUS MINIMUM LAP OR WELD). B. PRECAST PAD: SURFACE MOUNTED CAPACITOR PAD, (SEE TABLE). OPENING SHALL BE FILLED WITH MINIMUM OF 1" IN CRUSHED ROCK FLUSH WITH TOP SURFACE. C. CONDUIT RISERS SHALL BE LOCATED PER DIMENSIONS IN THE PLAN VIEW ON SHEET 1 AND ROUTED PER WORK ORDER DRAWINGS. PLUG CONDUIT ENDS PER CU 1600-96G. D. FOR GROUND ROD & CLAMP MATERIAL REQUIREMENTS, SEE CO 782. E. CONDUITS, GROUNDING, BACKFILL AND COMPACTION TO BE COMPLETED AND INSPECTED PRIOR TO PLACEMENT OF PAD. F. NO VAULT IS REQUIRED UNDER THE PAD FOR THE INSTALLATION OF PADMOUNT CAPACITOR BANKS. 14' EASEMENT 3' 8' 3' 8' 22' EASEMENT 8' 6' ITEM QTY DESCRIPTION ANAHEIM PART NO. COMPATIBLE UNIT 1 .87 YDS CONCRETE, CLASS A, 5 SACK MIX - - SEE NOTE A 2 95 LF REINFORCING BAR #4 DIA.) - - SEE NOTE A 3 1 PAD, PRECAST (SEE TABLE) - - SEE NOTE B 4 2 GROUND ROD, k" x 8' LONG 547005 SEE NOTE D 5 2 CLAMP, ROD 568075 SEE NOTE D 6 15FT WIRE #4 BARE CU. SOLID, SOFT 446150 W4CUBARE-SD 7 - - - - PSC 6'X8' PAD EASEMENT 14'X22'