SCOPE: THIS STANDARD SHOWS CUSTOMER INSTALLED U.G. ELECTRIC SERVICE TO SPRINKLER CONTROLLERS. 1 OR 1 1 36" MIN. RISER POLE CONDUIT AND CONDUCTOR LEGEND 2 3 1y" GRAY PVC SCHED. 40 1y" GRAY PVC D.B. 1 2 3 1 1y" RIGID GALV. STEEL PULL BOX UTILITY FEED 2 36" MIN. 3 36" MIN. 36" MIN. SEE NOTE G 2 2 2 POLE SEE NOTE D GRIP 12" TAG PER NOTE F SWEEP, GROUND PER CO 784 (SEE NOTE E) TO UTILITY O.H. SECONDARY CONDUCTORS VERIFY LENGTH WITH UTILITY INSPECTOR EXTEND 8' MIN. ABOVE GRADE FOR SERVICE FROM PMT SEE CU 1600-21 13" X 24" PULL BOX PER CONST. STD. CU 1500-1A GND. ROD & CONNECTOR PER CO 782 (SEE NOTE E) 18" MAX. SPRINKLER CONTROL CABINET 15 AMP MAX. BREAKER IN SEALED UNMETERED SERVICE ENTRANCE HUB WITH TAMPERPROOF BOLTS SERVICE ENTRANCE ENCLOSURE 4O AMP MIN., NEMA 3R BREAKER ENCLOSURE, (G.E. NO. TL240RCU) WITH 15 AMP MAX. PLUG IN BREAKER (TWO POLE 15 AMP- GE # THQL2115, SINGLE POLE- GE #THQL1115). POUR 24" x 24" x 12" CONCRETE BASE AFTER SUPPORT AND CONDUIT INSTALLATION (SEE PAGE STENCIL ADDRESS ON STREET SIDE AND INSIDE OF COVER PADMOUNT TRANSFORMER (PMT) OR SUBSURFACE TRANSFORMER (BURD) CONDUCTORS FOR 3-#6 CU THHN OR THW MIN. APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS PREP BY SYS PLN MGR SUB MAINT NEW SHEET NEW SHEET FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : CUSTOMER INSTALLED U.G. ELECTRIC SERVICE TO SPRINKLER CONTROLLERS CU 1600-26 REV 8 8 07-21 1 2 CU 1600-26 15A MAX. ---PAGE BREAK--- METHOD OF SUPPORTING BREAKER ENCLOSURE DETAIL NOTES: 1y"x1y"x 3/16" BY 36" LONG ANGLE BOLT OR WELD MOUNTING PLATE TO ANGLES SIZE MOUNTING PLATE TO BREAKER ENCLOSURE WELD PLATE TO PIPE u" FILLETS FULL LENGTH, BOTH SIZES 2" IPS BY 36" LONG SUPPORT PIPE DEBURR PLATE & SUPPORT(S). APPLY 2 COATS GRAY RUST-O-LEUM PAINT OVER PRIMER. SUPPORT(S) TO EXTEND THRU 24"x24"x3y" CONCRETE BASE. A. ELECTRICAL SERVICE SHALL BE PROVIDED IN ACCORDANCE WITH CITY OF ANAHEIM RATES, RULES AND REGULATIONS, RULE 9.A.3, FOR UNMETERED SERVICE, UPON REQUEST (IN WRITING) WHERE THE APPLICANT FOR SERVICE HAS A FIXED CONNECTED LOAD. B. ELECTRICAL PERMIT MUST BE OBTAINED FROM CITY OF ANAHEIM BUILDING DEPARTMENT PRIOR TO START OF WORK. ASSIGNED ADDRESS SHALL BE STENCILED ON STREET SIDE OF SERVICE ENTRANCE ENCLOSURE. C. CONTRACTOR TO FURNISH ALL TRENCHING, BACKFILL, COMPACTION AND MATERIAL INCLUDING CONDUIT AND CONDUCTORS FROM SERVICE ENTRANCE ENCLOSURE TO UTILITIES DESIGNATED POINT OF SERVICE AS SHOWN ON ELECTRICAL DIVISION WORK ORDER DRAWING. VERIFY WITH ELECTRICAL DIVISION UTILITY INSPECTOR. D. RISER, IF REQUIRED, SHALL BE INSTALLED ON FACE OF RISER POLE AWAY FROM TRAFFIC OR AS DESIGNATED ON ELECTRICAL DIVISION WORK ORDER DRAWING. CONTRACTOR SHALL PROVIDE KELLUM GRIP OF CORRECT SIZE TO SUPPORT CONDUCTORS IN RISER. E. CONTRACTOR SHALL FURNISH AND INSTALL GROUNDING MATERIAL FOR HDG (GALVINIZED STEEL) CONDUIT PER CO 784 CO 782. F. ELECTRICAL DIVISION FIELD CREW TO BUILD RISER, ASSIST CONTRACTOR IN PULLING OF SERVICE CONDUCTORS FROM SERVICE ENTRANCE ENCLOSURE TO DESIGNATED POINT OF SERVICE AND TAG CONNECTORS PER CO 17O. SEAL SERVICE ENTRANCE ENCLOSURE UPON ENERGIZING. G. DEPTH, SIZE AND TYPE OF CONDUIT AND CONDUCTORS FROM SERVICE ENTRANCE ENCLOSURE (BREAKER SECTION) TO SPRINKLER CONTROL CABINET SHALL BE SPECIFIED BY: APPROPRIATE DEPARTMENT OF CITY OF ANAHEIM, IF CITY OWNED. CITY OF ANAHEIM BUILDING DEPARMENT, ELECTRICAL INSPECTOR SECTION, IF RESIDENTIAL OR COMMERCIAL / INDUSTRIAL INSTALLATION. APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT OPS MGR T&D CONSTRUCTION STANDARDS PREP BY SYS PLN MGR SUB MAINT NEW SHEET NEW SHEET FILENAME: REVISION KEYS: ADDED / REVISED TEXT CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : CUSTOMER INSTALLED U.G. ELECTRIC SERVICE TO SPRINKLER CONTROLLERS CU 1600-26 REV 8 8 07-21 2 2 CU 1600-26